A universal WLD (Water Leak Detection) sensor, with one WLD sensing cable input and 2 kinds of outputs.
- Relay Output: Sensor WLD Relay requires an external 12V power supply, OK / Water / Disconnected states of WLD detection input are signaled by relay output (NO/NC).
- 1W-UNI (RJ11) Output: Sensor WLD Relay is connected by RJ11 cable to any HWg device (STE2, Poseidon, Ares, ...) as a standard external sensor.
Sensor WLD Relay is input for one WLD zone. Several sensors can be used with one Poseidon / Ares device for WLD detection in several zones.
The WLD sensing cable detects water along the entire length of the cable. Soaking or interrupting of cable can switch the relay contact.
WLD Relay is part of HWg Monitoring Ecosystem (sensors + devices + SensDesk Technology portal), that gets you long-term reliable alerts, graphs, PDF reports, open API, remote device management, etc. The right Water Detection and early alert are essential in a lot of businesses, for example, data centers, etc. Water Leak Detection System from HW group is a complex solution developed to protect your facility against costly water damage that might threaten you.
>> Read the article about Water Leak Detection (WLD) System.
- External WLD sensor for all RJ11 (1W-UNI) devices (Poseidon2, Ares, STE2, ...)
- Sensor WLD Relay 1W-UNI is powered from RJ11
- WLD input is 1 water detection zone up to 185 meters
- Even the smallest volume of water, ethylene glycol, or other conductive liquid is detected anywhere along the entire length of the sensing cable
- WLD by HWg is unique long-term stable technology because of none Bend / Twist / Grip limits
- Water leak detector for security systems
- Water detection under raised floors
- Leaky pipe detection (cable wrapped along the pipe)
- Protection against floods from roof lights (sensing cable routed along the walls)
- Detection of water leaks in drip trays
- Detection of water leaks under air-conditioning outlets
WLD relay installation
Sensor WLD Relay can be used as a Standalone WLD sensor (power + relay output) or as a 1W-UNI sensor connected to any STE2, Poseidon2, HWg-Ares, or other HWg devices.
WLD sensing cable
WLD sensing cable detects liquid along the entire length of the sensing cable. Even a few drops of water, ethylene glycol, or other conductive liquid trigger the alarm. WLD sensing cable is re-usable (cable can be cleaned, dried & used again).
WLD sensing cable features
- No Bend limit: WLD sensing cable is not limited by any bending radius.
- No Twist limit: WLD sensing cable can be twisted as any other electrical cable.
- No Grip limit: Water detection functionality is not limited by point pressure within a reasonable range.
WLD cable components
WLD sensing cable is supplied in length from 2m to 50m and can be extended by a non-sensing WLD prolong cable.
- Connection cable - 2m (Green terminal block, 2m, Terminator)
- WLD Sensing cable A - 2m / 10m / 50m
- WLD prolong cable A - 5m
Why is Water Leak Detection system better than Flood detector
Water Leak Detection with the sensing cable is more expensive than simple spot water detection. However, WLD provides a much faster reaction to any water in the room. Thanks to the early alert significant damages to IT or other infrastructure can be avoided. Water Leak Detection with sensing cable is recommended in IT, data centers, technology, the medical sector, or anywhere else, where any water damage would be highly expensive.
Proper Water Leak Detection with a sensing cable helps you avoid costly damages thanks to an early alert that is triggered by the first few drops of liquid. Learn more about the difference between the WLD system with sensing cable and water spot detection in the application note.
>> Water Detection: Sensing cable versus Flood sensor
Sensor WLD Relay - HWg Video Flyer
HWg Video about Water Leak Detection system and it's components
Knowledge Base articles about Water Leak Detection System
Fast & reliable detection of the first drops of water in remote locations is critical for many businesses. Early water leak detection isn't just important for data centers and medical labs, it also saves significant money in industrial facilities, physical archive storage, hotels, museums and more. To bring you reliable & early water leak detection, in HW group we created the sensing cable type A - the heart of the water leak detection system.
Read the Knowledge Base article about the heart of the WLD system - the sensing cable.
The business of reliable water detection in buildings is about really fast water detection and fast alarming (and alert escalation). To detect water in a building (nearby protected technology) within the first 5-15 minutes costs the end customer tens of hundreds of Euros. If a customer has invested time & money in analyzing where to install the sensing cable for water detection, the communication/alarm escalation must also be properly implemented.
Read the Knowledge Base article about components of the WLD system by HW group.
There are two principles for detecting water in remote locations - Spot Detection or Water Leak Detection based on Sensing cable. They cost different amounts of money (hardware & installation), but also give different results. Let's take a closer look.
Read the Knowledge Base article about the difference between Water Spot Detection and WLD Zone Detection.
WLD Relay - a universal WLD (Water Leak Detection) sensor, with one WLD sensing cable input and 2 kinds of outputs, is one of our top-selling products. Here's why.
Read the Knowledge Base Article about the top selling WLD components: Sensor WLD Relay 1W-UNI.
Recommended products
WLD sensing cable A
WLD sensing cable type A. Water is detected along the entire length of the WLD sensing cable.
WLD prolong cable A
Prolong non-sensitive cable 5m for WLD type A. Can be extended to up to 100m in total.
WLD sensing cable A
WLD sensing cable type A. Water is detected along the entire length of the WLD sensing cable.
WLD2
WLD2 is a WiFi / Ethernet water leak detector with support for WWW, SNMP and PoE. To detect leaking liquids, it uses 4 sensing cables
SD-WLD
1x Water Leak Detection zone (sensing cable) to the portal. LAN and WiFi connectivity, IoT Monitoring unit (Portal required).
NB-2x1Wire
4 external RJ11 sensors values to the portal (Temperature, Relative Humidity, Current, ...).
STE2 R2
WiFi and Ethernet, PoE available, temperature and humidity sensor with digital inputs. Up to 5 sensors of any RJ11 type.
Ares 12 LTE
Industrial measuring and monitoring for 14 sensors with GSM and LTE communication and back-up power.